(Build It) Right First Time

The title of this 1979 Th’ Dudes song could be a mantra for the residential construction industry.

Codewords 102: August 2021

Article is relevant to LBP licence classes: All

Every year home owners spend significant amounts of time and money on house construction. For this investment they expect, as a minimum, a building that keeps the water out long-term.

The work of MBIE's Weathertight Services Technical Team puts us in a good position to identify recurring areas of weathertightness failures. It is worth noting that most of these failures are for buildings between 10 and 30 years old and therefore not built in accordance with the current Acceptable Solutions of the New Zealand Building Code.

Here are 7 of the most common. To illustrate these failures we have kept our words to a minimum, instead using photos and accompanying text from a building assessor's reports.

1. Membrane roofs/gutters, scuppers and decks

These commonly show failures at joints, adherence to other materials or at upturns and downturns of membrane sheets.

Butyl rubber membrane over a small roof. Inadequate front edge installation with the corner cut exposing the plywood substrate.

Butyl rubber membrane over a small roof. Inadequate front edge installation with the corner cut exposing the plywood substrate.

2. Kick-out flashings at wall and roof junctions

The absence of a kick-out flashing allows water to flow behind the cladding.

Photograph: No kick-out or diverter provision at the bottom end of the apron junction to a fibre-cement cladding. Destructive testing confirms water ingress and timber damage.

No kick-out or diverter provision at the bottom end of the apron junction to a fibre-cement cladding. Destructive testing confirms water ingress and timber damage.

3. Thresholds to decks

The junctions between the walls, joinery, balustrades and decks are prone to water ingress due to inadequate threshold heights, folds and corners or cladding proximity to membranes.

Photograph: Stucco plaster cladding and joinery close to a tiled deck.

Stucco plaster cladding and joinery close to a tiled deck. Joinery installation issues at the jamb. Minimal threshold separation allows water uptake into the uncoated, porous bottom edge of the stucco plaster. Maintenance difficulties.

4. Parapets, balustrades and attachment points.

Water entry can cause structural damage to parapets and solid balustrades at either capping or gutter and deck levels due to lack of saddle-flashings, cross fall, expansion joints and plan change direction. Damage to structure can also occur where open balustrades are fixed through membranes, solid balustrades, and walls.

Photograph of top fixed stainless-steel and timber handrails penetrating an EIFS clad parapet with clear signs of water ingress around the penetration points.

Top fixed stainless-steel handrail penetrates an EIFS clad parapet. There are clear signs of water ingress around the penetration point with the coating cracks indicating moisture movement to the underlying timber framing. The steel bracket-fixed timber post directly penetrates the cladding. This cannot be made weathertight or be adequately maintained.

5. Joints and flashings in cladding

These are often inadequate allowing water ingress and damage particularly at horizontal and control joints.

Photo showing an example of water ingress behind cladding.

Stucco plaster cladding over rigid backing. Incorrect control joint formation, without separation of mesh and plaster over the joint, leading to movement cracking and water ingress.

6. Joinery installation

Head, jamb and sill flashings fail to deflect water to the exterior or are non-existent.

Photograph of non-existant flashings which fail to adequately deflect water.

Texture-coated fibre-cement cladding. Window head flashings without stop-ends or other means of preventing water ingress. Coating and cladding sheets are in contact with the shoulder of the flashing which allows water uptake to the cladding edges by capillary action. Timber testing reveals visible water staining and a very high moisture reading. No evidence of proprietary waterproofing systems installation to window perimeter.

7. Ground clearances

Unpaved and paved ground levels are too high, failing to protect either cladding or framing. This requires particular care at garage door openings where driveways are close to floor level for ease of vehicle entry.

Photograph showing the damaged wood framing.

A fibre-cement clad timber-framed column and built-up paving resulting in significant damage.

The Leaky Home crisis has given us all a greater understanding of how moisture enters and damages a building. Fortunately we can now build to prevent, minimise and manage water ingress and egress, enhancing the building's life and providing homes that are healthy

Legislation, building practices and controls have and are being updated to help manage the problem. MBIE's Building Code Update 2021 consultation document proposes options for raising performance standards. Conservatively this could bring New Zealand's Code up to comparable international standards, or boldly, above these standards, leading the way whilst simultaneously meeting our energy efficiency and wider climate-change obligations.

Regardless, we must remind ourselves to learn from the past and (Build it) Right First Time.

Author

Ron Esveld
Senior Advisor Quality Assurance, Weathertight Services.
FNZIA (Fellow, New Zealand Institute of Architects)
Ministry of Business, Innovation and Employment

Photographs

Frank Wiemann
NZIBS (New Zealand Institute of Building Surveyors)
AKNDS (Registered Architect and Engineer, Germany)
Section 1 Building Consultants

Quiz:

  1. The Weathertight Services Technical Team is a part of which organisation?
    1. Ministry of Business, Innovation and Employment (MBIE)
    2. BRANZ
    3. Th' Dudes
    4. MetService weather forecasting
  1. How old are most of the buildings where weathertightness failures have been found?
    1. 2 years
    2. Between 5 and 10 years
    3. Between 10 and 30 years
    4. 30 years or older
  1. Which of the following are common weathertightness failures?
    1. Thresholds to decks
    2. Joints and flashings in claddings
    3. Exterior joinery installation
    4. Poor ground clearances
    5. All of the above

Check answers

  1. The Weathertight Services Technical Team is a part of which organisation?
    1. Ministry of Business, Innovation and Employment (MBIE).
  1. How old are most of the buildings where weathertightness failures have been found?
    1. Between 10 and 30 years.
  1. Which of the following are common weathertightness failures?
    1. All of the above.